Fiber optic, photonic & electronic test & measurement
Cleveland Electric Labs

FiberStrike Linear Heat Series DTS (Distributed Temperature Sensing / Linear Heat Detection)

A distributed temperature sensing controller and passive sensor cable that measures temperature continuously along a fiber, used for linear heat / fire detection and continuous asset temperature monitoring.

Technical overview

The Linear Heat Series device supports up to four channels over a monitoring range of up to 10 km with spatial resolution down to 0.5 m, and provides 44 extendable relay outputs and four inputs with 256 user-definable zones carrying 5+2 alarm criteria. Interfaces are USB, Ethernet and Modbus TCP. The sensor cable is a completely passive fiber optic cable rated to -40 to +85 (150) degrees C. CEL states the DTS retains monitoring capability at temperatures up to 750 C / 1382 F and carries VdS EN 54-22, UL521, ULC S530, FM 3210, ATEX II(1) GD M2, KFI, CCC and SIL2 certifications. The same platform underpins CEL's CBTM bus duct and CSTM switchgear temperature monitoring offerings.

Features

  • Passive sensor cable, maintenance free, immune to dirt, dust, humidity, corrosion and EMI
  • Gapless monitoring and complete asset coverage
  • Accurately tracks the size and direction of a spreading fire regardless of air currents
  • Low laser power, suited to ATEX/IECEx hazardous environments
  • Easy to integrate into existing fire alarm systems
  • Differentiates fire from seasonal temperature increases based on temperature delta
  • SmartVision GUI provides visual overview of alarm zones, operational status and real-time temperatures

Specifications

Specifications
ParameterValue
Monitoring rangeUp to 10 km
ChannelsUp to 4
Spatial resolutiondown to 0.5 m
Relays44 outputs (extendable) / 4 Inputs
User definable zones256 with 5+2 alarm criteria
Operating temperature range (device)10 to +60 C (recorded exactly as published by CEL; the sign and degree symbol are absent in the source) degC
InterfacesUSB, Ethernet, Modbus TCP
Certifications (device)VdS, UL, FM, IECex, SIL2
Sensor fiber operating temperature-40 to +85 (150) C degC
Sensor fiber localization<1 m spatial resolution m
Sensor fiber reachup to 10 km
Detection speedFast detection (10 measurement time) - the unit is omitted in CEL's source and has not been guessed
Maximum survivable temperature retaining monitoring capability750 C (1382 F) degC
Sampling intervalless than one m
Single passive fiber rangeup to 10 km
Fire certificationsVdS EN 54-22, UL521, ULC S530, FM 3210, ATEX II(1) GD M2, KFI, CCC, SIL2
Specifications are reproduced from the manufacturer's own published material on the date shown and are subject to change. Confirm at order.

Applications

  • Special hazard fire detection
  • Aircraft hangars
  • Chemical plants
  • Coal storage facilities
  • Mining conveyor belts
  • Continuous bus duct temperature monitoring (CBTM)
  • Continuous switchgear temperature monitoring (CSTM)
  • Data center electrical infrastructure monitoring
  • Pipeline leak detection
Manufacturer datasheet (PDF)

You may also like

Need help specifying this?

Our application engineers will confirm specifications with the manufacturer and quote for your configuration.

Request Info